Cooling capacity12.8kW43,700 BTU/h
Heating capacity13.8kW
Cooling power input0.185kW
Source catalogue ↗
·
PRODUCT OVERVIEW

Samsung AM128ANHPKH/EU — Duct S · High static

Samsung AM128ANHPKH/EU has a rated cooling capacity of 12.8 kW (43,700 BTU/h). High-static Duct S indoor units serve ducted air distribution. Select airflow together with duct resistance and the manufacturer’s static-pressure limits.

Key features

01

Design and function

High-static Duct S indoor units serve ducted air distribution. Select airflow together with duct resistance and the manufacturer’s static-pressure limits.

02

Airflow and sound by fan speed

High/Medium/Low values retain the manufacturer’s table order. Power input for AM128ANHPKH/EU is indoor-unit input and excludes the outdoor unit; rated cooling capacity is 12.8 kW.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

AM128ANHPKH/EU · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · AM128ANHPKH/EU
Cooling capacity (kW)12.8
Cooling capacity (BTU/h)43,700
Heating capacity (kW)13.8

Electrical & efficiency3

Electrical & efficiency · AM128ANHPKH/EU
Power supply220~240 V · 1 phase · 2 wires · 50/60 Hz
Cooling power input (kW)0.185
Heating power input (kW)0.185

Airflow & sound3

Airflow & sound · AM128ANHPKH/EU
Catalogue airflow (m³/h)2220/1800/1320
Sound pressure in catalogue order · dB(A)39/36/33
Static pressure (Min/Std/Max) · Pa29.42/60.80/196.13

Dimensions & weight2

Dimensions & weight · AM128ANHPKH/EU
Dimensions H × W × D (mm)300 × 1300 × 700
Net weight (kg)44.5

Refrigerant & piping3

Refrigerant & piping · AM128ANHPKH/EU
RefrigerantR410A
Liquid pipe (mm)9.52
Gas pipe (mm)15.88

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial projects according to equipment type. Heat load and zone requirements determine the appropriate configuration.

Selection considerations

Match the complete model code and regional suffix. Correct actual capacity for temperatures, pipe length and height difference; verify configuration and compatibility using Samsung documentation or selection tools. Optional functions depend on supplied accessories and controllers.

Overview referenceSamsung DVM S2 / DVM S Eco (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Samsung DVM S2 / DVM S Eco (EN) · PDF page 169.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/