VI
← Browse this series
LGConcealed duct · High static
LG Concealed duct · High static
Product range illustration · Source catalogue ↗

ARNU76GB8A4

LG · Concealed duct · High static

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity22.4kW76,400 BTU/h
Heating capacity25.2kW
Net weight87kg
Source catalogue ↗
·
PRODUCT OVERVIEW

LG ARNU76GB8A4 — Concealed duct · High static

LG ARNU76GB8A4 has a rated cooling capacity of 22.4 kW (76,400 BTU/h). High-static ducted indoor units serve duct systems with higher resistance. Use fan characteristics to select the required airflow and static pressure together.

Key features

01

Design and function

High-static ducted indoor units serve duct systems with higher resistance. Use fan characteristics to select the required airflow and static pressure together.

02

Power input by fan speed

The catalogue lists ARNU76GB8A4 power input as 765 / 500 / 500 W in fan-speed order. This is indoor-unit input and excludes outdoor-unit power.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

ARNU76GB8A4 · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · ARNU76GB8A4
Cooling capacity (kW)22.4
Cooling capacity (BTU/h)76,400
Heating capacity (kW)25.2

Electrical & efficiency2

Electrical & efficiency · ARNU76GB8A4
Power supply220-230-240 V · 1 phase · 50/60 Hz
Power input (H/M/L) · W765 / 500 / 500

Airflow & sound3

Airflow & sound · ARNU76GB8A4
Sound pressure (H/M/L) · dB(A)45 / 41 / 40
Airflow (H/M/L) · m³/min64.0 / 50.0 / 50.0
Catalogue static pressure · mmAq (Pa)22(216)

Dimensions & weight2

Dimensions & weight · ARNU76GB8A4
Dimensions H × W × D (mm)460 × 1562 × 688
Net weight (kg)87

Refrigerant & piping2

Refrigerant & piping · ARNU76GB8A4
Liquid pipe (mm)Ø 9.52 (3/8)
Gas pipe (mm)Ø 19.05 (3/4)

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, retail or multi-zone projects according to equipment type. Heat load, installation position and usage determine the appropriate solution.

Selection considerations

Check model codes, power supply, connection ratios, accessories and rating conditions. Actual capacity must account for piping length, height difference and working temperatures using LG documentation or selection software.

Overview referenceLG MULTI V · Indoor Units (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference LG MULTI V · Indoor Units (EN) · PDF page 25.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The Vietnamese and English editions use matching verified model codes; each language links to its corresponding catalogue. Dimensions are reordered from the manufacturer’s W × H × D to the website’s H × W × D.

Fan speeds retain H/M/L (High/Medium/Low) order; floor-standing units use SH/H/M/L (Super High/High/Medium/Low). A dash marks an unlisted speed. Refrigerant and compatibility must be checked against the selected outdoor unit.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/