VI
← Browse this series
LGMulti V i · Heat pump
LG Multi V i · Heat pump
Product range illustration · Source catalogue ↗

ARUN660LTE6

LG · Multi V i · Heat pump · 66 HP

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity184.8kW630,600 BTU/h
EER4.38W/W
Cooling power input42.2kW
Source catalogue ↗
·
PRODUCT OVERVIEW

LG ARUN660LTE6 — Multi V i · Heat pump

LG ARUN660LTE6 has a rated cooling capacity of 184.8 kW (630,600 BTU/h). LG inverter heat-pump outdoor units with separate cooling and heating ratings. Multi V i features an AI Engine, control functions and system diagnostic support tools.

Key features

01

Design and function

LG inverter heat-pump outdoor units with separate cooling and heating ratings. Multi V i features an AI Engine, control functions and system diagnostic support tools.

02

AI and diagnostic support

The AI Engine supports operation management. AI Smart Diagnosis and Black Box data require LGMV tools; network functions depend on compatible controllers, connectivity and services.

03

Flexible outdoor-unit combinations

The catalogue provides standard combinations and a Free Combination function. The 26 HP module is excluded from Free Combination; verify configurations using LATS and the Product Data Book.

04

Noise control

Noise Target Control supports an operating sound target. The specification table gives rated sound-pressure levels; assess noise-control operation against capacity and operating conditions.

TECHNICAL DATA

Technical specifications

ARUN660LTE6 · Rated values from the manufacturer catalogue

Rated capacity4

Rated capacity · ARUN660LTE6
Capacity HP66
Cooling capacity (kW)184.8
Cooling capacity (BTU/h)630,600
Heating capacity (kW)205.3

Electrical & efficiency4

Electrical & efficiency · ARUN660LTE6
Power supply380 ~ 400 ~ 415 V · 3 phase · 50 Hz
Cooling power input (kW)42.2
Heating power input (kW)47.2
EER (W/W)4.38

Airflow & sound3

Airflow & sound · ARUN660LTE6
Sound pressure (Cooling / Heating) · dB(A)68.8 / 69.8
Airflow as printed in the catalogue (m³/min)(320 × 1) + (320 × 1) + (320 × 1)
Catalogue static pressure (Pa)80

Dimensions & weight1

Dimensions & weight · ARUN660LTE6
Weight calculated as printed in the catalogue (kg)829

Refrigerant & piping3

Refrigerant & piping · ARUN660LTE6
RefrigerantR410A
Liquid pipe (mm)Ø 22.2 (7/8)
Gas pipe (mm)Ø 53.98 (2-1/8)

Other specifications1

Other specifications · ARUN660LTE6
Maximum indoor units (conditional limit in parentheses)64

Combination component units

Dimensions below describe each module. Total weight is calculated by adding component weights; installation dimensions must include manufacturer-specified clearances.

ComponentH × W × D (mm)kg
ARUN240LTE61745 × 1240 × 760283
ARUN240LTE61745 × 1240 × 760283
ARUN180LTE61745 × 1240 × 760263

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, retail or multi-zone projects according to equipment type. Heat load, installation position and usage determine the appropriate solution.

Selection considerations

Check model codes, power supply, connection ratios, accessories and rating conditions. Actual capacity must account for piping length, height difference and working temperatures using LG documentation or selection software.

Overview referenceLG MULTI V i (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference LG MULTI V i (EN) · PDF page 21.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The Vietnamese and English editions use matching verified model codes; each language links to its corresponding catalogue. Dimensions are reordered from the manufacturer’s W × H × D to the website’s H × W × D.

The indoor-unit count in parentheses is a conditional connection limit, not the default allowance. Combination sound-pressure ratings retain the manufacturer’s table values and are not arithmetic sums of component levels.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/