PRODUCT OVERVIEW
LG ARUV681LLS5 — Multi V 5 Pro II · Cooling only
LG ARUV681LLS5 has a rated cooling capacity of 190.4 kW (649,700 BTU/h). R410A inverter outdoor units for cooling only. Multi V 5 Pro II offers Dual Sensing Control, a Black Fin heat exchanger and multi-module combination configurations.
Key features
01
Design and function
R410A inverter outdoor units for cooling only. Multi V 5 Pro II offers Dual Sensing Control, a Black Fin heat exchanger and multi-module combination configurations.
02
Dual Sensing Control
Temperature and humidity sensing adapts operation to indoor conditions. The catalogue requires a Standard III wired remote controller for this function; the controller is sold separately.
03
Black Fin heat exchanger
The Black Fin coating is described as improving resistance to environmental corrosion, including salt and pollutants. Installation and maintenance must still account for actual site conditions.
04
Cooling-only configurations
The ARUV models in this catalogue are cooling-only units, including single and multi-module configurations. Multi V i heating ratings do not apply to Multi V 5 Pro II.
ARUV681LLS5 · Rated values from the manufacturer catalogue
Rated capacity3
Rated capacity · ARUV681LLS5| Capacity HP | 68 |
|---|
| Cooling capacity (kW) | 190.4 |
|---|
| Cooling capacity (BTU/h) | 649,700 |
|---|
Electrical & efficiency3
Electrical & efficiency · ARUV681LLS5| Power supply | 380~415 V · 3 phase · 50 Hz |
|---|
| Cooling power input (kW) | 53.5 |
|---|
| EER (W/W) | 3.56 |
|---|
Airflow & sound3
Airflow & sound · ARUV681LLS5| Cooling sound pressure · dB(A) | 68.7 |
|---|
| Airflow as printed in the catalogue (m³/min) | 320 × 3 |
|---|
| Catalogue static pressure (Pa) | 80 |
|---|
Dimensions & weight1
Dimensions & weight · ARUV681LLS5| Weight calculated as printed in the catalogue (kg) | 708.5 |
|---|
Refrigerant & piping3
Refrigerant & piping · ARUV681LLS5| Refrigerant | R410A |
|---|
| Liquid pipe (mm) | Ø 22.2 (7/8) |
|---|
| Gas pipe (mm) | Ø 53.98 (2-1/8) |
|---|
Other specifications1
Other specifications · ARUV681LLS5| Maximum indoor units (conditional limit in parentheses) | 64 |
|---|
Combination component units
Dimensions below describe each module. Total weight is calculated by adding component weights; installation dimensions must include manufacturer-specified clearances.
No matching specifications. Try another keyword.
Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →
Applications & layout
Consider for offices, hotels, retail or multi-zone projects according to equipment type. Heat load, installation position and usage determine the appropriate solution.
Selection considerations
Check model codes, power supply, connection ratios, accessories and rating conditions. Actual capacity must account for piping length, height difference and working temperatures using LG documentation or selection software.
Overview referenceLG MULTI V 5 PRO II (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION
Catalogue & notes
Model specifications reference LG MULTI V 5 PRO II (EN) · PDF page 14.
Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.
The Vietnamese and English editions use matching verified model codes; each language links to its corresponding catalogue. Dimensions are reordered from the manufacturer’s W × H × D to the website’s H × W × D.
The indoor-unit count in parentheses is a conditional connection limit, not the default allowance. Combination sound-pressure ratings retain the manufacturer’s table values and are not arithmetic sums of component levels.