FDC112KXEN6

Mitsubishi Heavy · Micro KX · Heat pump · 4 HP

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity11.2kW≈ 38,200 BTU/h
Heating capacity12.5kW
Cooling power input2.8kW
Source catalogue ↗
·
PRODUCT OVERVIEW

FDC112KXEN6 — Mitsubishi Heavy Micro KX · Heat pump

Mitsubishi Heavy FDC112KXEN6 has a rated cooling capacity of 11.2 kW. Micro KX uses inverter technology and a side-discharge outdoor unit for multi-indoor-unit systems. Check capacity ratios and indoor-unit counts for each code.

Key features

01

Design and function

Micro KX uses inverter technology and a side-discharge outdoor unit for multi-indoor-unit systems. Check capacity ratios and indoor-unit counts for each code.

02

R410A refrigerant system

The FDC112KXEN6 version uses a R410A system. Select compatible outdoor units, indoor units and accessories; R32 and R410A indoor units are not interchangeable.

TECHNICAL DATA

Technical specifications

FDC112KXEN6 · Rated values from the manufacturer catalogue

Rated capacity4

Rated capacity · FDC112KXEN6
Capacity HP4
Cooling capacity (kW)11.2
Converted cooling capacity (BTU/h)38,200
Heating capacity (kW)12.5

Electrical & efficiency2

Electrical & efficiency · FDC112KXEN6
Power supply1 Phase 220-240V, 50Hz
Cooling power input (kW)2.8

Airflow & sound1

Airflow & sound · FDC112KXEN6
Sound pressure in catalogue order (dB(A))52/54

Dimensions & weight2

Dimensions & weight · FDC112KXEN6
Dimensions H × W × D (mm)845 × 970 × 370
Net weight (kg)85

Refrigerant & piping1

Refrigerant & piping · FDC112KXEN6
RefrigerantR410A

Other specifications2

Other specifications · FDC112KXEN6
Connected capacity ratio (%)80-150
Maximum connectable indoor units6

BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial projects according to equipment type and actual heat load. Piping, air distribution and controls must be designed for the project.

Selection considerations

Check components, power supply and rating conditions against the manufacturer table. Combination weights retain the published values; individual module dimensions are not overall installation dimensions. High Head -K codes are component-only models as stated in the catalogue.

Overview referenceMitsubishi Heavy KXZ PLUS · 26KX02E (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Mitsubishi Heavy KXZ PLUS · 26KX02E (EN) · PDF page 66.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/