VI
← Browse this series
Mitsubishi HeavyKXZ2 PLUS · Cooling only
Mitsubishi Heavy KXZ2 PLUS · Cooling only
Product range illustration · Source catalogue ↗

FDC280CKXZA2S

Mitsubishi Heavy · KXZ2 PLUS · Cooling only · 10 HP

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity28kW≈ 95,500 BTU/h
Net weight288kg
Cooling power input7.25kW
Source catalogue ↗
·
PRODUCT OVERVIEW

FDC280CKXZA2S — Mitsubishi Heavy KXZ2 PLUS · Cooling only

Mitsubishi Heavy FDC280CKXZA2S has a rated cooling capacity of 28 kW. KXZ2 PLUS uses inverter technology with individual outdoor units and combination configurations. The catalogue describes high-ambient cooling capability; check the applicable operating limits and conditions.

Key features

01

Design and function

KXZ2 PLUS uses inverter technology with individual outdoor units and combination configurations. The catalogue describes high-ambient cooling capability; check the applicable operating limits and conditions.

02

R410A refrigerant system

The FDC280CKXZA2S version uses a R410A system. Select compatible outdoor units, indoor units and accessories; R32 and R410A indoor units are not interchangeable.

TECHNICAL DATA

Technical specifications

FDC280CKXZA2S · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · FDC280CKXZA2S
Capacity HP10
Cooling capacity (kW)28
Converted cooling capacity (BTU/h)95,500

Electrical & efficiency2

Electrical & efficiency · FDC280CKXZA2S
Power supply3 Phase 380-415V, 50Hz
Cooling power input (kW)7.25

Airflow & sound1

Airflow & sound · FDC280CKXZA2S
Sound pressure in catalogue order (dB(A))56

Dimensions & weight2

Dimensions & weight · FDC280CKXZA2S
Dimensions H × W × D (mm)1697 × 1350 × 720
Net weight (kg)288

Refrigerant & piping1

Refrigerant & piping · FDC280CKXZA2S
RefrigerantR410A

Other specifications2

Other specifications · FDC280CKXZA2S
Connected capacity ratio (%)50-200
Maximum connectable indoor units37

BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial projects according to equipment type and actual heat load. Piping, air distribution and controls must be designed for the project.

Selection considerations

Check components, power supply and rating conditions against the manufacturer table. Combination weights retain the published values; individual module dimensions are not overall installation dimensions. High Head -K codes are component-only models as stated in the catalogue.

Overview referenceMitsubishi Heavy KXZ PLUS · 26KX02E (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Mitsubishi Heavy KXZ PLUS · 26KX02E (EN) · PDF page 30.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

VRF central air conditioning system design & installation