Cooling capacity28kW≈ 95,500 BTU/h
Heating capacity31.5kW
Cooling power input8.09kW
Source catalogue ↗
·
PRODUCT OVERVIEW

FDC280KXE6G — Mitsubishi Heavy KX Lite · Heat pump

Mitsubishi Heavy FDC280KXE6G has a rated cooling capacity of 28 kW. KX Lite uses a two-fan side-discharge layout. Capacity and indoor-unit connection limits are published for each model.

Key features

01

Design and function

KX Lite uses a two-fan side-discharge layout. Capacity and indoor-unit connection limits are published for each model.

02

R410A refrigerant system

The FDC280KXE6G version uses a R410A system. Select compatible outdoor units, indoor units and accessories; R32 and R410A indoor units are not interchangeable.

TECHNICAL DATA

Technical specifications

FDC280KXE6G · Rated values from the manufacturer catalogue

Rated capacity4

Rated capacity · FDC280KXE6G
Capacity HP10
Cooling capacity (kW)28
Converted cooling capacity (BTU/h)95,500
Heating capacity (kW)31.5

Electrical & efficiency2

Electrical & efficiency · FDC280KXE6G
Power supply3 Phase 380-415V, 50Hz
Cooling power input (kW)8.09

Airflow & sound1

Airflow & sound · FDC280KXE6G
Sound pressure in catalogue order (dB(A))59/60

Dimensions & weight2

Dimensions & weight · FDC280KXE6G
Dimensions H × W × D (mm)1675 × 1080 × 480
Net weight (kg)215

Refrigerant & piping1

Refrigerant & piping · FDC280KXE6G
RefrigerantR410A

Other specifications2

Other specifications · FDC280KXE6G
Connected capacity ratio (%)50-150
Maximum connectable indoor units24

BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial projects according to equipment type and actual heat load. Piping, air distribution and controls must be designed for the project.

Selection considerations

Check components, power supply and rating conditions against the manufacturer table. Combination weights retain the published values; individual module dimensions are not overall installation dimensions. High Head -K codes are component-only models as stated in the catalogue.

Overview referenceMitsubishi Heavy KXZ PLUS · 26KX02E (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Mitsubishi Heavy KXZ PLUS · 26KX02E (EN) · PDF page 68.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/