VI
← Browse this series
Mitsubishi HeavyCompact 4-way cassette · FDTC
Mitsubishi Heavy Compact 4-way cassette · FDTC
Product range illustration · Source catalogue ↗

FDTC28KXZE1-W

Mitsubishi Heavy · Compact 4-way cassette · FDTC

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity2.8kW≈ 9,600 BTU/h
Heating capacity3.2kW
Cooling power input0.03kW
Source catalogue ↗
·
PRODUCT OVERVIEW

FDTC28KXZE1-W — Mitsubishi Heavy Compact 4-way cassette · FDTC

Mitsubishi Heavy FDTC28KXZE1-W has a rated cooling capacity of 2.8 kW. FDTC fits a 600 × 600 mm ceiling grid. The catalogue includes grid and honeycomb panels, with an optional draft-prevention panel.

Key features

01

Design and function

FDTC fits a 600 × 600 mm ceiling grid. The catalogue includes grid and honeycomb panels, with an optional draft-prevention panel.

02

R32 refrigerant system

The FDTC28KXZE1-W version uses a R32 system. Select compatible outdoor units, indoor units and accessories; R32 and R410A indoor units are not interchangeable.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

FDTC28KXZE1-W · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · FDTC28KXZE1-W
Cooling capacity (kW)2.8
Converted cooling capacity (BTU/h)9,600
Heating capacity (kW)3.2

Electrical & efficiency2

Electrical & efficiency · FDTC28KXZE1-W
Power supply1 Phase 220-240V, 50Hz
Cooling power input (kW)0.03

Airflow & sound3

Airflow & sound · FDTC28KXZE1-W
Sound pressure in catalogue order (dB(A))P-Hi:35 Hi:32 Me:29 Lo:25
Catalogue sound power level (dB(A))49
Airflow in catalogue order (m³/min)P-Hi:9 Hi:8 Me:7 Lo:6

Dimensions & weight4

Dimensions & weight · FDTC28KXZE1-W
Dimensions H × W × D (mm)248 × 570 × 570
Net weight (kg)13
Panel weight (kg)2.5
Panel dimensions H × W × D (mm)10 × 620 × 620

Refrigerant & piping1

Refrigerant & piping · FDTC28KXZE1-W
RefrigerantR32

BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial projects according to equipment type and actual heat load. Piping, air distribution and controls must be designed for the project.

Selection considerations

Check refrigerant, 50/60 Hz supply, connection ratio, piping lengths and accessories against manufacturer requirements. R32 and R410A indoor units must not be treated as interchangeable. Indoor heating ratings apply only when the system supports heating.

Overview referenceMitsubishi Heavy KXZ PLUS · 26KX02E (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Mitsubishi Heavy KXZ PLUS · 26KX02E (EN) · PDF page 86.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/