Cooling capacity22.4kW≈ 76,400 BTU/h
Heating capacity16kW
Net weight89kg
Source catalogue ↗
·
PRODUCT OVERVIEW

FDU1800FKXZE1 — Mitsubishi Heavy Outdoor-air processing · FDU-F

Mitsubishi Heavy FDU1800FKXZE1 has a rated cooling capacity of 22.4 kW. FDU-F treats outdoor air and does not replace room air conditioning. The catalogue requires additional room conditioning and checks of outdoor-air conditions and connection ratios.

Key features

01

Design and function

FDU-F treats outdoor air and does not replace room air conditioning. The catalogue requires additional room conditioning and checks of outdoor-air conditions and connection ratios.

02

R410A refrigerant system

The FDU1800FKXZE1 version uses a R410A system. Select compatible outdoor units, indoor units and accessories; R32 and R410A indoor units are not interchangeable.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

FDU1800FKXZE1 · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · FDU1800FKXZE1
Cooling capacity (kW)22.4
Converted cooling capacity (BTU/h)76,400
Heating capacity (kW)16

Electrical & efficiency2

Electrical & efficiency · FDU1800FKXZE1
Power supply1 Phase 220-240V, 50Hz
Cooling power input (kW)1.16-1.20

Airflow & sound3

Airflow & sound · FDU1800FKXZE1
Sound pressure in catalogue order (dB(A))Hi:42
Airflow in catalogue order (m³/min)Hi:30
Catalogue static pressure (Pa)200 (at Hi Air flow)

Dimensions & weight2

Dimensions & weight · FDU1800FKXZE1
Dimensions H × W × D (mm)379 × 1600 × 893
Net weight (kg)89

Refrigerant & piping1

Refrigerant & piping · FDU1800FKXZE1
RefrigerantR410A

BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial projects according to equipment type and actual heat load. Piping, air distribution and controls must be designed for the project.

Selection considerations

Check refrigerant, 50/60 Hz supply, connection ratio, piping lengths and accessories against manufacturer requirements. R32 and R410A indoor units must not be treated as interchangeable. Indoor heating ratings apply only when the system supports heating.

Overview referenceMitsubishi Heavy KXZ PLUS · 26KX02E (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Mitsubishi Heavy KXZ PLUS · 26KX02E (EN) · PDF page 118.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/