PRODUCT OVERVIEW
Gree GMV-400WML/A1-X — GMV9 Flex · Anti-corrosion
Gree GMV-400WML/A1-X belongs to the GMV9 Flex · Anti-corrosion range in the GMV catalogue. The published cooling capacity is 40 kW.
Key features
01
Product range and ratings
Consult the model table for its ratings and manufacturer test conditions.
GMV-400WML/A1-X · Rated values from the manufacturer catalogue
Rated capacity6
Rated capacity · GMV-400WML/A1-X| Capacity HP | 14 |
|---|
| Cooling capacity (kW) | 40 |
|---|
| Converted cooling capacity (BTU/h) | 136,500 |
|---|
| Maximum cooling capacity (kW) | 40 |
|---|
| Heating capacity (kW) | 40 |
|---|
| Maximum heating capacity (kW) | 45 |
|---|
Electrical & efficiency7
Electrical & efficiency · GMV-400WML/A1-X| Power supply | 380–415 V · 3N~ · 50/60 Hz |
|---|
| Minimum circuit current (A) | 31.5 |
|---|
| Maximum fuse current (A) | 32 |
|---|
| SEER with ducted units | 7.15 |
|---|
| SEER with cassette units | 7.2 |
|---|
| SCOP with ducted units | 4.56 |
|---|
| SCOP with cassette units | 4.5 |
|---|
Airflow & sound2
Airflow & sound · GMV-400WML/A1-X| Normal sound pressure (dB(A)) | 59 |
|---|
| Catalogue airflow (m³/h) | 19000 |
|---|
Dimensions & weight2
Dimensions & weight · GMV-400WML/A1-X| Dimensions H × W × D (mm) | 1745 × 1250 × 460 |
|---|
| Net weight (kg) | 210 |
|---|
Refrigerant & piping3
Refrigerant & piping · GMV-400WML/A1-X| Refrigerant charge (kg) | 7 |
|---|
| Liquid pipe (mm) | Φ12.7(1/2) |
|---|
| Gas pipe (mm) | Φ25.4(1) |
|---|
BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.
No matching specifications. Try another keyword.
Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →
Applications & layout
Check the installation format, design load and accessories against the catalogue drawings.
Selection considerations
Confirm outdoor and indoor unit combinations and the power supply against Gree documentation before selection.
Overview referenceGree GMV6 / GMV VRF (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION
Catalogue & notes
Model specifications reference Gree GMV6 / GMV VRF (EN) · PDF page 49.
Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.
The original English catalogue is shared by both languages; Vietnamese editorial content is translated.