PRODUCT OVERVIEW
Toshiba MMD-VN802HEX1E — Heat recovery ventilation with DX coil
Toshiba MMD-VN802HEX1E belongs to the Heat recovery ventilation with DX coil range, with a rated cooling capacity of 6.56 kW. This page brings together specifications, a range illustration and a link to the original SMMS-u catalogue table.
Key features
01
Heat exchange with a DX coil
Total cooling and heating capacities already include the recovered heat shown in catalogue parentheses. Do not add it again. EH/H/L are operating settings; slash-separated values retain 50/60 Hz order.
02
Traceable specifications
Values come from the model-specific table. BTU/h is converted from kW; shared range illustrations do not replace installation drawings.
Indoor-unit power input excludes the outdoor unit’s power consumption.
Total cooling and heating capacities already include the recovered heat shown in catalogue parentheses. Do not add it again. EH/H/L are operating settings; slash-separated values retain 50/60 Hz order.
MMD-VN802HEX1E · Rated values from the manufacturer catalogue
Rated capacity3
Rated capacity · MMD-VN802HEX1E| Cooling capacity (kW) | 6.56 |
|---|
| Converted cooling capacity (BTU/h) | 22,400 |
|---|
| Heating capacity (kW) | 8.61 |
|---|
Electrical & efficiency2
Electrical & efficiency · MMD-VN802HEX1E| Power supply | 1 phase 50Hz 230V (220-240V) / 1 phase 60Hz 220V |
|---|
| EH/H/L power input · each pair 50/60 Hz (W) | EH: 505/595; H: 465/555; L: 335/390 |
|---|
Airflow & sound4
Airflow & sound · MMD-VN802HEX1E| EH/H/L airflow · each pair 50/60 Hz (m³/h) | EH: 800/-; H: 800/-; L: 640/600 |
|---|
| EH/H/L sound pressure · each pair 50/60 Hz (dB(A)) | EH: 41/43; H: 40/42; L: 38/37 |
|---|
| Catalogue sound power level (dB(A)) | 58 |
|---|
| Catalogue static pressure (Pa) | EH: 120/190; H: 100/155; L: 100/130 |
|---|
Dimensions & weight2
Dimensions & weight · MMD-VN802HEX1E| Dimensions H × W × D (mm) | 430 × 1189 × 1739 |
|---|
| Net weight (kg) | 100 |
|---|
Refrigerant & piping2
Refrigerant & piping · MMD-VN802HEX1E| Liquid pipe (mm) | 6.4 |
|---|
| Gas pipe (mm) | 12.7 |
|---|
Other specifications2
Other specifications · MMD-VN802HEX1E| Recovered heat included in cooling capacity (kW) | 2.06 |
|---|
| Recovered heat included in heating capacity (kW) | 3.61 |
|---|
BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.
No matching specifications. Try another keyword.
Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →
Applications & layout
Consider the range for commercial, office or residential projects according to its intended installation format. Size the actual system for cooling load, ventilation, sound and available space.
Selection considerations
Check power supply, rating conditions, outdoor/indoor combinations and accessories against Toshiba documentation. Both languages share the English catalogue; capacity alone does not establish compatibility.
Overview referenceToshiba SMMS-u (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION
Catalogue & notes
Model specifications reference Toshiba SMMS-u (EN) · PDF page 46.
Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.
Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.
The original English catalogue is shared by both languages; Vietnamese editorial content is translated.