PRODUCT OVERVIEW
PUCY-EP550YSKE — Mitsubishi Electric cooling-only outdoor unit
Mitsubishi Electric PUCY-EP550YSKE belongs to the CITY MULTI system, with a rated cooling capacity of 62.4 kW (212,900 BTU/h). PUCY YKE offers P Standard, GP High Standard and EP High Efficiency ranges, with ratings recorded separately for each model.
Key features
01
Equipment type and layout
PUCY YKE offers P Standard, GP High Standard and EP High Efficiency ranges, with ratings recorded separately for each model.
02
Model-specific specifications
The specification table for PUCY-EP550YSKE links to the original catalogue page. Model suffixes and electrical variants are kept separate for reference.
PUCY-EP550YSKE · Rated values from the manufacturer catalogue
Rated capacity2
Rated capacity · PUCY-EP550YSKE| Cooling capacity (kW) | 62.4 |
|---|
| Cooling capacity (BTU/h) | 212,900 |
|---|
Electrical & efficiency3
Electrical & efficiency · PUCY-EP550YSKE| Power supply | 3-phase 4-wire 380-400-415V 50/60Hz |
|---|
| Cooling power input (kW) | 13.56 |
|---|
| EER (W/W) | 4.6 |
|---|
Airflow & sound1
Airflow & sound · PUCY-EP550YSKE| Sound pressure in catalogue order (dB(A)) | 62.5 |
|---|
Dimensions & weight1
Dimensions & weight · PUCY-EP550YSKE| Sum of component unit weights, calculated (kg) | 432 |
|---|
Refrigerant & piping3
Refrigerant & piping · PUCY-EP550YSKE| Refrigerant | R410A |
|---|
| Liquid pipe (mm) | 15.88 (5/8) Brazed |
|---|
| Gas pipe (mm) | 28.58 (1-1/8) Brazed |
|---|
Other specifications1
Other specifications · PUCY-EP550YSKE| EER per TCVN 13256:2021 (W/W) | 7.07 |
|---|
Combination component units
Dimensions below describe each module. Total weight is calculated by adding component weights; installation dimensions must include manufacturer-specified clearances.
No matching specifications. Try another keyword.
Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →
Applications & layout
Consider for offices, hotels, residences or commercial buildings according to equipment type and requirements. Select capacity based on heat load and system design.
Selection considerations
For combination codes, check component units, connection ratios and corrected capacity for site conditions. The catalogue -BS suffix denotes an anti-corrosion option; these records use the base model code.
Overview referenceMitsubishi Electric CITY MULTI · VIFeatures describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION
Catalogue & notes
Model specifications reference Mitsubishi Electric CITY MULTI · VI · PDF page 75.
Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.