PUCY-P1500YSKE

Mitsubishi Electric · Cooling-only outdoor unit · CITY MULTI PUCY-P YKE

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity168kW573,200 BTU/h
EER3.61W/W
Cooling power input46.53kW
Source catalogue ↗
·
PRODUCT OVERVIEW

PUCY-P1500YSKE — Mitsubishi Electric cooling-only outdoor unit

Mitsubishi Electric PUCY-P1500YSKE belongs to the CITY MULTI system, with a rated cooling capacity of 168 kW (573,200 BTU/h). PUCY YKE offers P Standard, GP High Standard and EP High Efficiency ranges, with ratings recorded separately for each model.

Key features

01

Equipment type and layout

PUCY YKE offers P Standard, GP High Standard and EP High Efficiency ranges, with ratings recorded separately for each model.

02

Model-specific specifications

The specification table for PUCY-P1500YSKE links to the original catalogue page. Model suffixes and electrical variants are kept separate for reference.

TECHNICAL DATA

Technical specifications

PUCY-P1500YSKE · Rated values from the manufacturer catalogue

Rated capacity2

Rated capacity · PUCY-P1500YSKE
Cooling capacity (kW)168
Cooling capacity (BTU/h)573,200

Electrical & efficiency3

Electrical & efficiency · PUCY-P1500YSKE
Power supply3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling power input (kW)46.53
EER (W/W)3.61

Airflow & sound1

Airflow & sound · PUCY-P1500YSKE
Sound pressure in catalogue order (dB(A))70.0

Dimensions & weight1

Dimensions & weight · PUCY-P1500YSKE
Sum of component unit weights, calculated (kg)780

Refrigerant & piping2

Refrigerant & piping · PUCY-P1500YSKE
Liquid pipe (mm)19.05 (3/4) Brazed
Gas pipe (mm)41.28 (1-5/8) Brazed

Other specifications1

Other specifications · PUCY-P1500YSKE
EER per TCVN 13256:2021 (W/W)5.62

Combination component units

Dimensions below describe each module. Total weight is calculated by adding component weights; installation dimensions must include manufacturer-specified clearances.

ComponentH × W × D (mm)kg
PUCY-P500YKE.TH1650 × 1750 × 740260
PUCY-P500YKE.TH1650 × 1750 × 740260
PUCY-P500YKE.TH1650 × 1750 × 740260

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial buildings according to equipment type and requirements. Select capacity based on heat load and system design.

Selection considerations

For combination codes, check component units, connection ratios and corrected capacity for site conditions. The catalogue -BS suffix denotes an anti-corrosion option; these records use the base model code.

Overview referenceMitsubishi Electric CITY MULTI · VIFeatures describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Mitsubishi Electric CITY MULTI · VI · PDF page 66.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.