Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity80kW273,000 BTU/h
EER4.05W/W
Cooling power input19.75kW
Source catalogue ↗
·
PRODUCT OVERVIEW

PUHY-EP700YSKD — Mitsubishi Electric heat-pump outdoor unit

Mitsubishi Electric PUHY-EP700YSKD belongs to the CITY MULTI system, with a rated cooling capacity of 80 kW (273,000 BTU/h). PUHY YKD provides cooling and heating. Combination models require checking their component units in the source table.

Key features

01

Equipment type and layout

PUHY YKD provides cooling and heating. Combination models require checking their component units in the source table.

02

Model-specific specifications

The specification table for PUHY-EP700YSKD links to the original catalogue page. Model suffixes and electrical variants are kept separate for reference.

TECHNICAL DATA

Technical specifications

PUHY-EP700YSKD · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · PUHY-EP700YSKD
Cooling capacity (kW)80
Cooling capacity (BTU/h)273,000
Heating capacity (kW)80

Electrical & efficiency3

Electrical & efficiency · PUHY-EP700YSKD
Power supply3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling power input (kW)19.75
EER (W/W)4.05

Airflow & sound1

Airflow & sound · PUHY-EP700YSKD
Sound pressure in catalogue order (dB(A))64

Dimensions & weight1

Dimensions & weight · PUHY-EP700YSKD
Sum of component unit weights, calculated (kg)486

Refrigerant & piping2

Refrigerant & piping · PUHY-EP700YSKD
Liquid pipe (mm)19.05 (3/4) Brazed
Gas pipe (mm)34.93 (1-3/8) Brazed

Combination component units

Dimensions below describe each module. Total weight is calculated by adding component weights; installation dimensions must include manufacturer-specified clearances.

ComponentH × W × D (mm)kg
PUHY-P350YKD.TH1650 × 1220 × 740243
PUHY-P350YKD.TH1650 × 1220 × 740243

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial buildings according to equipment type and requirements. Select capacity based on heat load and system design.

Selection considerations

For combination codes, check component units, connection ratios and corrected capacity for site conditions. The catalogue -BS suffix denotes an anti-corrosion option; these records use the base model code.

Overview referenceMitsubishi Electric CITY MULTI · VIFeatures describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Mitsubishi Electric CITY MULTI · VI · PDF page 94.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.