PRODUCT OVERVIEW
Hitachi RAS-50HNBBMQ · SET FREE Σ HNBQ · Heat pump
Hitachi RAS-50HNBBMQ belongs to the SET FREE Σ HNBQ · Heat pump range with a cooling capacity of 140 kW. This page provides model specifications, range illustrations and links to the source catalogue page.
Key features
01
Scroll compressor and inverter control
The SET FREE Σ range uses scroll compressors and R410A. Capacity and power input are specified for each model.
02
Single units and module combinations
The tables cover single units and combinations. Check the module configuration, weight and dimensions for the exact combination code.
03
Flexible piping design
The catalogue lists total piping up to 1,000 m and actual length up to 165 m under specified conditions. Check these limits together with height differences and accessories.
04
Operating mode
HNBQ is a heat-pump system with cooling and heating modes. Heating ratings require a compatible equipment combination.
RAS-50HNBBMQ · Rated values from the manufacturer catalogue
System configuration1
System configuration · RAS-50HNBBMQ| Maximum connectable indoor units | 64 |
|---|
Rated capacity4
Rated capacity · RAS-50HNBBMQ| Capacity HP | 50 |
|---|
| Cooling capacity (kW) | 140 |
|---|
| Converted cooling capacity (BTU/h) | 477,700 |
|---|
| Heating capacity (kW) | 156 |
|---|
Electrical & efficiency7
Electrical & efficiency · RAS-50HNBBMQ| Power supply | 380/400/415 V ±10% · 3N~ · 50 Hz |
|---|
| Maximum operating current (A) | 43.5+43.5+45.0 |
|---|
| Breaker current rating (A) | 63+63+63 |
|---|
| Cooling power input (kW) | 36.25 |
|---|
| Heating power input (kW) | 35.7 |
|---|
| EER (W/W) | 3.86 |
|---|
| COP (W/W) | 4.37 |
|---|
Airflow & sound2
Airflow & sound · RAS-50HNBBMQ| Anechoic sound pressure · dB(A) | 66 |
|---|
| Airflow in catalogue order (m³/min) | 256+256+329 |
|---|
Dimensions & weight2
Dimensions & weight · RAS-50HNBBMQ| Dimensions H × W × D (mm) | 1725 × 4044 × 782 |
|---|
| Net weight as printed in the catalogue (kg) | 1102 |
|---|
Refrigerant & piping4
Refrigerant & piping · RAS-50HNBBMQ| Refrigerant | R410A |
|---|
| Refrigerant charge (kg) | 24.2 |
|---|
| Liquid pipe (mm) | Ø19.05(3/4) |
|---|
| Gas pipe (mm) | Ø44.5(1-3/4) |
|---|
Other specifications2
Other specifications · RAS-50HNBBMQ| Module combination (HP) | 16+16+18 |
|---|
| Connected capacity ratio (%) | 50–140 |
|---|
BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.
No matching specifications. Try another keyword.
Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →
Applications & layout
May be considered for multi-zone air conditioning in offices, hotels and commercial buildings. Configuration depends on load, operating mode and installation conditions.
Selection considerations
The English catalogue is shared by Vietnamese and English pages. Ratings follow the manufacturer’s test conditions. Confirm combinations, correction factors and accessories before design.
Overview referenceHitachi SET FREE Σ HNBQ Heat Pump (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION
Catalogue & notes
Model specifications reference Hitachi SET FREE Σ HNBQ Heat Pump (EN) · PDF page 12.
Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.
Combination configurations and dimensions retain the catalogue figures. Weight expressions with plus signs show individual module weights. Check installation clearances and piping connections against the manufacturer’s technical drawings.