VI
← Browse this series
HitachiSET FREE Σ CNCQ · Cooling only
Hitachi SET FREE Σ CNCQ · Cooling only
Product range illustration · Source catalogue ↗

RAS-66CNBCMQ

Hitachi · SET FREE Σ CNCQ · Cooling only · 66 HP

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity186kW635,000 BTU/h
EER3.01W/W
Cooling power input61.8kW
Source catalogue ↗
·
PRODUCT OVERVIEW

Hitachi RAS-66CNBCMQ · SET FREE Σ CNCQ · Cooling only

Hitachi RAS-66CNBCMQ belongs to the SET FREE Σ CNCQ · Cooling only range with a cooling capacity of 186 kW. This page provides model specifications, range illustrations and links to the source catalogue page.

Key features

01

Scroll compressor and inverter control

The SET FREE Σ range uses scroll compressors and R410A. Capacity and power input are specified for each model.

02

Single units and module combinations

The tables cover single units and combinations. Check the module configuration, weight and dimensions for the exact combination code.

03

Flexible piping design

The catalogue lists total piping up to 1,000 m and actual length up to 165 m under specified conditions. Check these limits together with height differences and accessories.

04

Operating mode

CNCQ is a cooling-only range. Website power input and EER use the catalogue nominal cooling row.

TECHNICAL DATA

Technical specifications

RAS-66CNBCMQ · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · RAS-66CNBCMQ
Capacity HP66
Cooling capacity (kW)186
Cooling capacity (BTU/h)635,000

Electrical & efficiency3

Electrical & efficiency · RAS-66CNBCMQ
Power supply380–415 V · 3N~ · 50 Hz
Cooling power input (kW)61.8
EER (W/W)3.01

Airflow & sound2

Airflow & sound · RAS-66CNBCMQ
Normal-mode sound pressure · dB(A)70
Airflow in catalogue order (m³/min)256+348+348

Dimensions & weight2

Dimensions & weight · RAS-66CNBCMQ
Dimensions H × W × D (mm)1725 × 4474 × 782
Net weight as printed in the catalogue (kg)341+403+403

Refrigerant & piping4

Refrigerant & piping · RAS-66CNBCMQ
RefrigerantR410A
Refrigerant charge (kg)35.9
Liquid pipe (mm)Ø19.05[3/4]
Gas pipe (mm)Ø44.45[1-3/4]

Other specifications2

Other specifications · RAS-66CNBCMQ
Module combination (HP)18+24+24
Connected capacity ratio (%)50–130

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

May be considered for multi-zone air conditioning in offices, hotels and commercial buildings. Configuration depends on load, operating mode and installation conditions.

Selection considerations

The English catalogue is shared by Vietnamese and English pages. Ratings follow the manufacturer’s test conditions. Confirm combinations, correction factors and accessories before design.

Overview referenceHitachi SET FREE Σ CNCQ Cooling Only (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Hitachi SET FREE Σ CNCQ Cooling Only (EN) · PDF page 13.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

Combination configurations and dimensions retain the catalogue figures. Weight expressions with plus signs show individual module weights. Check installation clearances and piping connections against the manufacturer’s technical drawings.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/