VI
← Browse this series
HitachiTwo-way cassette · RCD
Hitachi Two-way cassette · RCD
Product range illustration · Source catalogue ↗

RCD-1.0FSN3

Hitachi · Two-way cassette · RCD

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity2.8kW≈ 9,600 BTU/h
Heating capacity3.2kW
Net weight23kg
Source catalogue ↗
·
PRODUCT OVERVIEW

Hitachi RCD-1.0FSN3 · Two-way cassette · RCD

Hitachi RCD-1.0FSN3 belongs to the Two-way cassette · RCD range with a cooling capacity of 2.8 kW. This page provides model specifications, range illustrations and links to the source catalogue page.

Key features

01

Two-way airflow

The two-way cassette layout can suit long, narrow spaces. Unit and panel dimensions vary by capacity group.

02

Model-specific specifications

Dimensions, weight, airflow and sound reference the exact model table. Check panels and accessories separately.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

RCD-1.0FSN3 · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · RCD-1.0FSN3
Cooling capacity (kW)2.8
Converted cooling capacity (BTU/h)9,600
Heating capacity (kW)3.2

Electrical & efficiency1

Electrical & efficiency · RCD-1.0FSN3
Power supply220–240 V / 50 Hz · 220 V / 60 Hz · 1~

Airflow & sound2

Airflow & sound · RCD-1.0FSN3
Sound pressure in catalogue order (dB(A))31/29/28/27
Airflow in catalogue order (m³/min)11/9.5/8.5/7

Dimensions & weight2

Dimensions & weight · RCD-1.0FSN3
Dimensions H × W × D (mm)298 × 860 × 630
Net weight (kg)23

Refrigerant & piping4

Refrigerant & piping · RCD-1.0FSN3
RefrigerantR410A
Liquid pipe (mm)Ø6.35
Gas pipe (mm)Ø12.7
Drain pipe sizeVP25

Differences between the two catalogues

The main table retains HNBQ catalogue values. The CNCQ catalogue lists different values below for the same model. Confirm the equipment version with the manufacturer before use.

Specification differences by source
Power supplyHNBQ · 220–240 V / 50 Hz · 220 V / 60 Hz · 1~
CNCQ · 220–240 V · 1~ · 50 Hz

HNBQ · PDF page 20 ↗ · CNCQ · PDF page 21 ↗

BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Select for the room layout, air distribution and installation space. Check cooling load, piping, drainage and service clearances.

Selection considerations

The English catalogue is shared by Vietnamese and English pages. Ratings follow the manufacturer’s test conditions. Confirm combinations, correction factors and accessories before design.

Overview referenceHitachi SET FREE Σ HNBQ Heat Pump (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Hitachi SET FREE Σ HNBQ Heat Pump (EN) · PDF page 20.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

Additional rating table — PDF page 21 ↗

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/