Cooling capacity56kW≈ 191,100 BTU/h
Heating capacity44.8kW
Net weight222kg
Source catalogue ↗
·
PRODUCT OVERVIEW

Hitachi RPI-20.0KFNQLF · Fresh air processing · RPI-KFNQ

Hitachi RPI-20.0KFNQLF belongs to the Fresh air processing · RPI-KFNQ range with a cooling capacity of 56 kW. This page provides model specifications, range illustrations and links to the source catalogue page.

Key features

01

Outdoor air processing

RPI-KFNQ units process fresh air. Room air-conditioning loads require other suitable indoor units in the system.

02

Check the connectable outdoor unit

The catalogue specifies connectable outdoor units and combination limits by model. Connectivity must be checked for the selected VRF outdoor unit.

03

Model-specific specifications

Dimensions, weight, airflow and sound reference the exact model table. Check panels and accessories separately.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

RPI-20.0KFNQLF · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · RPI-20.0KFNQLF
Cooling capacity (kW)56
Converted cooling capacity (BTU/h)191,100
Heating capacity (kW)44.8

Electrical & efficiency1

Electrical & efficiency · RPI-20.0KFNQLF
Power supply380–415 V · 3~ · 50 Hz

Airflow & sound3

Airflow & sound · RPI-20.0KFNQLF
Catalogue airflow (m³/h)6,000
Sound pressure in catalogue order (dB(A))63
Catalogue static pressure (Pa)200

Dimensions & weight2

Dimensions & weight · RPI-20.0KFNQLF
Dimensions H × W × D (mm)735 × 1950 × 805
Net weight (kg)222

Refrigerant & piping3

Refrigerant & piping · RPI-20.0KFNQLF
RefrigerantR410A
Liquid pipe (mm)Ø15.88
Gas pipe (mm)Ø28.6

BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Select for the room layout, air distribution and installation space. Check cooling load, piping, drainage and service clearances.

Selection considerations

The English catalogue is shared by Vietnamese and English pages. Ratings follow the manufacturer’s test conditions. Confirm combinations, correction factors and accessories before design.

Overview referenceHitachi SET FREE Σ HNBQ Heat Pump (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Hitachi SET FREE Σ HNBQ Heat Pump (EN) · PDF page 26.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.