VI
← Browse this series
HitachiHigh static pressure duct · RPIH / RPI-FSNQ
Hitachi High static pressure duct · RPIH / RPI-FSNQ
Product range illustration · Source catalogue ↗

RPI-8.0FSNQ

Hitachi · High static pressure duct · RPIH / RPI-FSNQ

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity22.4kW≈ 76,400 BTU/h
Heating capacity25kW
Net weight96kg
Source catalogue ↗
·
PRODUCT OVERVIEW

Hitachi RPI-8.0FSNQ · High static pressure duct · RPIH / RPI-FSNQ

Hitachi RPI-8.0FSNQ belongs to the High static pressure duct · RPIH / RPI-FSNQ range with a cooling capacity of 22.4 kW. This page provides model specifications, range illustrations and links to the source catalogue page.

Key features

01

Ductwork and static pressure

The high static pressure range supports concealed ducted layouts. Available pressure varies by model and must match duct resistance.

02

Model-specific specifications

Dimensions, weight, airflow and sound reference the exact model table. Check panels and accessories separately.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

RPI-8.0FSNQ · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · RPI-8.0FSNQ
Cooling capacity (kW)22.4
Converted cooling capacity (BTU/h)76,400
Heating capacity (kW)25

Electrical & efficiency1

Electrical & efficiency · RPI-8.0FSNQ
Power supply380–415 V · 3~ · 50 Hz

Airflow & sound3

Airflow & sound · RPI-8.0FSNQ
Sound pressure in catalogue order (dB(A))50
Airflow in catalogue order (m³/min)58
Catalogue static pressure (Pa)180

Dimensions & weight2

Dimensions & weight · RPI-8.0FSNQ
Dimensions H × W × D (mm)470 × 1060 × 1120
Net weight (kg)96

Refrigerant & piping4

Refrigerant & piping · RPI-8.0FSNQ
RefrigerantR410A
Liquid pipe (mm)Ø9.52
Gas pipe (mm)Ø19.05
Drain pipe sizeVP25

BTU/h is converted from the kW rating (1 kW ≈ 3,412.142 BTU/h) and rounded to 100 BTU/h; it is not a BTU/h figure printed in the catalogue.

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Select for the room layout, air distribution and installation space. Check cooling load, piping, drainage and service clearances.

Selection considerations

The English catalogue is shared by Vietnamese and English pages. Ratings follow the manufacturer’s test conditions. Confirm combinations, correction factors and accessories before design.

Overview referenceHitachi SET FREE Σ HNBQ Heat Pump (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Hitachi SET FREE Σ HNBQ Heat Pump (EN) · PDF page 21.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The original English catalogue is shared by both languages; Vietnamese editorial content is translated.

Additional rating table — PDF page 23 ↗

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/