PRODUCT OVERVIEW
Panasonic S-180ME2E5 – High static ducted E2
S-180ME2E5 belongs to the Panasonic FSV High static ducted E2 range, with rated cooling capacity of 18 kW (61,400 BTU/h).
Key features
01
Design & operation
Three static pressure settings: 60/140/270 Pa (72/140/270 Pa for the 28 kW model).
02
Model-specific ratings
Rated cooling capacity for S-180ME2E5 is 18 kW. Check rating conditions and accessories on the source catalogue page.
Indoor-unit power input excludes the outdoor unit’s power consumption.
S-180ME2E5 · Rated values from the manufacturer catalogue
Rated capacity2
Rated capacity · S-180ME2E5| Cooling capacity (kW) | 18 |
|---|
| Cooling capacity (BTU/h) | 61,400 |
|---|
Electrical & efficiency1
Electrical & efficiency · S-180ME2E5| Cooling power input (kW) | 0.400 |
|---|
Airflow & sound2
Airflow & sound · S-180ME2E5| Sound pressure (H/M/L) · dB(A) | 44/42/40 |
|---|
| Catalogue airflow (m³/h) | 2,940/2,640/2,340 |
|---|
Dimensions & weight2
Dimensions & weight · S-180ME2E5| Dimensions H × W × D (mm) | 479 x 1,453 x 1,205 |
|---|
| Net weight (kg) | 102 |
|---|
Refrigerant & piping2
Refrigerant & piping · S-180ME2E5| Liquid pipe (mm) | 9.52 |
|---|
| Gas pipe (mm) | 19.05 |
|---|
No matching specifications. Try another keyword.
Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →
Applications & layout
Consider for offices, shops and rooms with a suitable ceiling layout. Plan for heat loads, airflow and maintenance access.
Selection considerations
Check controllers, accessories, drainage and outdoor-unit compatibility before selection. The illustration represents the product range.
Overview referenceCatalogue Panasonic FSV (EN).pdfFeatures describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION
Catalogue & notes
Model specifications reference Catalogue Panasonic FSV (EN).pdf · PDF page 37.
Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.
Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.