VI
← Browse this series
LGFresh-air processing unit
LG Fresh-air processing unit
Product range illustration · Source catalogue ↗

ARNU48GM3Z4

LG · Fresh-air processing unit

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity14.1kW48,100 BTU/h
Heating capacity13.5kW
Net weight42.6kg
Source catalogue ↗
·
PRODUCT OVERVIEW

LG ARNU48GM3Z4 — Fresh-air processing unit

LG ARNU48GM3Z4 has a rated cooling capacity of 14.1 kW (48,100 BTU/h). Outdoor-air processing units for Multi V have different rating conditions from recirculating indoor units. Their capacity must not be substituted directly for room-conditioning capacity.

Key features

01

Design and function

Outdoor-air processing units for Multi V have different rating conditions from recirculating indoor units. Their capacity must not be substituted directly for room-conditioning capacity.

02

Power input by fan speed

The catalogue lists ARNU48GM3Z4 power input as 75 / 47 / 47 W in fan-speed order. This is indoor-unit input and excludes outdoor-unit power.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

ARNU48GM3Z4 · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · ARNU48GM3Z4
Cooling capacity (kW)14.1
Cooling capacity (BTU/h)48,100
Heating capacity (kW)13.5

Electrical & efficiency2

Electrical & efficiency · ARNU48GM3Z4
Power supply220-230-240 V · 1 phase · 50/60 Hz
Power input (H/M/L) · W75 / 47 / 47

Airflow & sound3

Airflow & sound · ARNU48GM3Z4
Sound pressure (H/M/L) · dB(A)38 / 36 / 36
Airflow (H/M/L) · m³/min20 / 13.2 / 13.2
Catalogue static pressure · mmAq (Pa)6 (59)

Dimensions & weight2

Dimensions & weight · ARNU48GM3Z4
Dimensions H × W × D (mm)360 × 1250 × 700
Net weight (kg)42.6

Refrigerant & piping2

Refrigerant & piping · ARNU48GM3Z4
Liquid pipe (mm)Ø 9.52 (3/8)
Gas pipe (mm)Ø 15.88 (5/8)

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

For outdoor-air treatment in a fresh-air supply design. Account for outdoor temperature, humidity, required airflow and the accompanying room-conditioning system.

Selection considerations

Check model codes, power supply, connection ratios, accessories and rating conditions. Actual capacity must account for piping length, height difference and working temperatures using LG documentation or selection software.

Overview referenceLG MULTI V · Indoor Units (EN)Features describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference LG MULTI V · Indoor Units (EN) · PDF page 27.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

The Vietnamese and English editions use matching verified model codes; each language links to its corresponding catalogue. Dimensions are reordered from the manufacturer’s W × H × D to the website’s H × W × D.

Fan speeds retain H/M/L (High/Medium/Low) order; floor-standing units use SH/H/M/L (Super High/High/Medium/Low). A dash marks an unlisted speed. Refrigerant and compatibility must be checked against the selected outdoor unit.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/