VI
← Browse this series
Mitsubishi ElectricHeat-pump outdoor unit · CITY MULTI PUHY-EP YKD
Mitsubishi Electric Heat-pump outdoor unit · CITY MULTI PUHY-EP YKD
Product range illustration · Source catalogue ↗

PUHY-EP400YSKD

Mitsubishi Electric · Heat-pump outdoor unit · CITY MULTI PUHY-EP YKD

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity44.8kW152,900 BTU/h
EER4.86W/W
Cooling power input9.21kW
Source catalogue ↗
·
PRODUCT OVERVIEW

PUHY-EP400YSKD — Mitsubishi Electric heat-pump outdoor unit

Mitsubishi Electric PUHY-EP400YSKD belongs to the CITY MULTI system, with a rated cooling capacity of 44.8 kW (152,900 BTU/h). PUHY YKD provides cooling and heating. Combination models require checking their component units in the source table.

Key features

01

Equipment type and layout

PUHY YKD provides cooling and heating. Combination models require checking their component units in the source table.

02

Model-specific specifications

The specification table for PUHY-EP400YSKD links to the original catalogue page. Model suffixes and electrical variants are kept separate for reference.

TECHNICAL DATA

Technical specifications

PUHY-EP400YSKD · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · PUHY-EP400YSKD
Cooling capacity (kW)44.8
Cooling capacity (BTU/h)152,900
Heating capacity (kW)44.8

Electrical & efficiency3

Electrical & efficiency · PUHY-EP400YSKD
Power supply3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling power input (kW)9.21
EER (W/W)4.86

Airflow & sound1

Airflow & sound · PUHY-EP400YSKD
Sound pressure in catalogue order (dB(A))60

Dimensions & weight1

Dimensions & weight · PUHY-EP400YSKD
Sum of component unit weights, calculated (kg)382

Refrigerant & piping2

Refrigerant & piping · PUHY-EP400YSKD
Liquid pipe (mm)12.7 (1/2) Brazed
Gas pipe (mm)28.58 (1-1/8) Brazed

Combination component units

Dimensions below describe each module. Total weight is calculated by adding component weights; installation dimensions must include manufacturer-specified clearances.

ComponentH × W × D (mm)kg
PUHY-P200YKD.TH1650 × 920 × 740191
PUHY-P200YKD.TH1650 × 920 × 740191

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider for offices, hotels, residences or commercial buildings according to equipment type and requirements. Select capacity based on heat load and system design.

Selection considerations

For combination codes, check component units, connection ratios and corrected capacity for site conditions. The catalogue -BS suffix denotes an anti-corrosion option; these records use the base model code.

Overview referenceMitsubishi Electric CITY MULTI · VIFeatures describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Mitsubishi Electric CITY MULTI · VI · PDF page 93.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

VRF central air conditioning system design & installation