VI
← Browse this series
PanasonicMH1H5
Panasonic MH1H5
Product range illustration · Source catalogue ↗
Indoor unitMH1H5 ↗

S-140MH1H5

Panasonic · MH1H5

Rated specifications and product information, referenced directly to the manufacturer catalogue.

Cooling capacity14kW47,800 BTU/h
Heating capacity13.2kW
Cooling power input0.430kW
Source catalogue ↗
·
PRODUCT OVERVIEW

Panasonic S-140MH1H5 – H1 high-fresh-air ducted unit

S-140MH1H5 belongs to Panasonic’s H1 High-Fresh Air Ducted range. The specification table lists a rated cooling capacity of 14 kW; selection must account for entering-air conditions and the building’s fresh-air treatment requirements.

Key features

01

Ducted fresh-air treatment

H1 is a ducted fresh-air treatment range. Interpret its rated capacity under H1 test conditions rather than directly comparing it with recirculating indoor units tested under different conditions.

TECHNICAL DATA

Technical specifications

Indoor-unit power input excludes the outdoor unit’s power consumption.

S-140MH1H5 · Rated values from the manufacturer catalogue

Rated capacity3

Rated capacity · S-140MH1H5
Cooling capacity (kW)14
Cooling capacity (BTU/h)47,800
Heating capacity (kW)13.2

Electrical & efficiency2

Electrical & efficiency · S-140MH1H5
Power supply220/230/240 V · 1 phase · 50 Hz
Cooling power input (kW)0.430

Airflow & sound2

Airflow & sound · S-140MH1H5
Sound pressure (220/230/240 V) · dB(A)43/44/44
Catalogue airflow (m³/h)1,560

Dimensions & weight2

Dimensions & weight · S-140MH1H5
Dimensions H × W × D (mm)420 x 1,065 x 620
Net weight (kg)50

Refrigerant & piping2

Refrigerant & piping · S-140MH1H5
Liquid pipe (mm)9.52
Gas pipe (mm)15.88

Cooling capacity and electrical power input are different quantities. Check catalogue test conditions when selecting equipment. Sources & notes →

Applications & layout

Consider as part of a building fresh-air supply design. Evaluate sensible load, latent load and ventilation requirements before system selection.

Selection considerations

The catalogue lists different accessories for cooling-only, cooling/heating and heat-recovery arrangements. Operation depends on the outdoor system and connection components; do not assume all modes are available in one configuration.

Overview referenceCatalogue Panasonic FSV (EN).pdfFeatures describe the product range; model-specific ratings appear in the specification table. Applications are suggestions based on equipment type.
SOURCE DOCUMENTATION

Catalogue & notes

Model specifications reference Catalogue Panasonic FSV (EN).pdf · PDF page 40.

Combined values retain the catalogue order for voltage, frequency or fan speed. Refer to the source-page notes before use.

Rated values depend on test conditions and system combinations. Confirm optional features against the supplied configuration. The source document and edition are recorded for each model on this page.

VRF central air conditioning system design & installation

SAVA M&E Joint Stock Company specializes in designing and installing VRF central air conditioning systems for factories, buildings and luxury villas. For enquiries, please contact SAVA M&E at: https://www.savame.com/lien-he/